Material: Aluminum, minimum 0.063 inches thick
Height: 10 inches
Width: 23.54 inches (overall), 20 inches (inside)
Length: 47.5 inches (overall), 31 inches (inside)
Enclosure Weight: A1024-HR-33 = 35.6 lbs., A1024-HR-00 = 34.1 lbs.
Weight Capacity: Door = 20 lbs., Enclosure total = 70 lbs.
Door Type: Continuously hinged,
swinging down/secured and gasketed for Type 12 rating (15.94 inch x 22.19 inch)
Equipment Mounting Plate: Door mounted, compatible with all
major manufacturers of jack/patch/punch panels and various manufacturers of hubs and routers (13.875 inch x 23.69 inch mounting space). See ACCESSORIES for plate types.
Cable Entry/Exit: 6 inch high x 3 inch long opening with approved re-enterable fire-rated foam kit.
Hubs and Routers: Stackable and rackable Hubs up to 2 rack spaces only, varies by manufacturer. Bay Networks, 3 Com, Cabletron, etc.
Electrical Access: 110V AC, 60 HZ, 15 Amp Max. Fan - 12V DC, 6-12 CFM. Filter UL® Listed.
Supports: Provide rod support angles, with drilled holes, at each corner of the box, above the ceiling.
There shall be provisions for the attachment of ceiling tile to the underside of the box and door.
8 Pin Modular Jack Capacity: 96
Copper Pair Capacity: 384 pair in, 384 pair out
Fiber Capacity: 192 Lucent Technologies LC Connector or, 96 ST Connectors or, 96 SC Connectors (Based on 96-RJ45 type openings)
Cable Capacity: Entrance: 24-25 pair Cat 5 or 3-72 fiber cables
Exit: Combination of, not to exceed 96, of 4 pair Cat 3, 4, or 5; 2 fiber plenum/non-plenum; 48-4 fiber plenum/ non-plenum; 32-6 fiber plenum/non-plenum cables.
|